Alabama Bids > Bid Detail

Chiller #1 Suction Flange and EEV Replacement

Agency: DEPT OF DEFENSE
Level of Government: Federal
Category:
  • J - Maintenance, Repair, and Rebuilding of Equipment
Opps ID: NBD00159395308974039
Posted Date: Jan 19, 2023
Due Date: Jan 23, 2023
Solicitation No: F6L32D3010AW01
Source: https://sam.gov/opp/f88144e69f...
Follow
Chiller #1 Suction Flange and EEV Replacement
Active
Contract Opportunity
Notice ID
F6L32D3010AW01
Related Notice
Department/Ind. Agency
DEPT OF DEFENSE
Sub-tier
DEPT OF THE ARMY
Major Command
NGB
Office
W7MT USPFO ACTIVITY ALANG 187
Looking for contract opportunity help?

Procurement Technical Assistance Centers (PTACs) are an official government contracting resource for small businesses. Find your local PTAC (opens in new window) for free government expertise related to contract opportunities.

General Information
  • Contract Opportunity Type: Sources Sought (Original)
  • All Dates/Times are: (UTC-06:00) CENTRAL STANDARD TIME, CHICAGO, USA
  • Original Published Date: Jan 19, 2023 11:15 am CST
  • Original Response Date: Jan 23, 2023 04:00 pm CST
  • Inactive Policy: 15 days after response date
  • Original Inactive Date:
  • Initiative:
    • None
Classification
  • Original Set Aside: Total Small Business Set-Aside (FAR 19.5)
  • Product Service Code: J041 - MAINT/REPAIR/REBUILD OF EQUIPMENT- REFRIGERATION, AIR CONDITIONING, AND AIR CIRCULATING EQUIPMENT
  • NAICS Code:
    • 238220 - Plumbing, Heating, and Air-Conditioning Contractors
  • Place of Performance:
    Montgomery , AL
    USA
Description

Seeking repair/replacement of failed EEV and leak in the flange between the compressor

and evaporator coil that needs to be replaced.



Airstack Chiller #1

M: ASP190FC15H1AS1EAAEN-R134A S: AF 02-075

Check in with customer upon arrival

Review scope of service

Perform proper lock out / tag out procedures

Preform Job Safety Analysis

Recover refrigerant per EPA guidelines

Disconnect and remove restricted EEV

Install new EEV

Replace filter driers

Remove and replace suction flange and gaskets

Pressurize system with nitrogen and leak check

Evacuate refrigerant circuit

Charge system with 500# of new 134-A refrigerant

Restore power to the unit

Perform start-up and verify proper operation

Clean work area

Submit XOI

Check out with customer



If your company has qualification to perform the above job on the referenced part number please submit a response to the Sources Sought to Adam.thibeault@us.af.mil


Attachments/Links
Contact Information
Contracting Office Address
  • KO FOR ALANG DO NOT DELETE 5187 SELMA HIGHWAY